Immersion Cooling B24 Dry Coolers Specification

Dry Coolers Specification

Model

FHWT120

FHDC240

Cooling Capacity120kW240kW
Circulation MediumOilOil
Input Voltage3-phase 350-480V 50/60Hz3-phase 350-480V 50/60Hz
Max Power Load (kW)48
Max Inlet/Outlet Temp (°C)45/6045/60
Reference Temperature (°C)3535
Total Air Volume (m³/h)3829956000
Dimensions (mm)2186*1874*21002520*2200*2160
Noise Level @25°C, 16m6568
Shipping Weight (kg)7691110
Operating Pressure (MPa)0.30.3
EC Fans
Automatic Speed Control
Model
FHDC480
FHDC1200
Cooling Capacity480kW1200kW
Circulation MediumWater/GlycolWater/Glycol
Input Voltage3-phase 350-480V 50/60Hz3-phase 350-480V 50/60Hz
Max Power Load (kW)1636
Max Inlet/Outlet Temp (°C)40/4540/45
Reference Temperature (°C)3535
Total Air Volume (m³/h)218543386826
Dimensions (mm)5250*1874*210011250*1874*2100
Noise Level @25°C, 16m7072
Shipping Weight (kg)22504710
Operating Pressure (MPa)0.40.4
EC Fans
Automatic Speed Control